
Variable Air Volume - VAV system HVAC
video description
Date: 2023-11-17
Related videos
Comments and reviews: 30
Clayton
Great video! Most of the information here is 100% correct, but if I may correct you on a few points:
1. You mentioned dirty air from the rooms can be chucked outside but this is not really the purpose of the relief path. The set of dampers after the return fan leading to the outside are typically modulated to maintain building static pressure in relation the outside. Typically the set point is somewhere around +0. 05 in. wc. This is necessary to keep your building positive so that unwanted air doesnt infiltrate around doors/windows from the outside. This way the outside air necessary for maintaining indoor air quality can be introduced through the AHU and can be conditioned as desired.
Dirty air is simply cleaned by the filters in the AHU and by always introducing some designed amount of fresh air through the outside air path.
2: There are typically two types of fan powered VAVs, either series or parallel. Your schematic shows the fan to not be in series with the airstream so that would be a parallel configuration in which typically the fan is only running when the zone calls for heat.
In a series configuration (not pictured) the fan is always running and the primary air from the AHU must pass through the fan. that is closer to how you described it which may be a little misleading.
3: Typically the duct static pressure sensor used to modulate the supply fan is mounted approximately 2/3 of the way down the primary air duct not at the end.
Anyways thanks for the video, nice work!
reply
Great video! Most of the information here is 100% correct, but if I may correct you on a few points:
1. You mentioned dirty air from the rooms can be chucked outside but this is not really the purpose of the relief path. The set of dampers after the return fan leading to the outside are typically modulated to maintain building static pressure in relation the outside. Typically the set point is somewhere around +0. 05 in. wc. This is necessary to keep your building positive so that unwanted air doesnt infiltrate around doors/windows from the outside. This way the outside air necessary for maintaining indoor air quality can be introduced through the AHU and can be conditioned as desired.
Dirty air is simply cleaned by the filters in the AHU and by always introducing some designed amount of fresh air through the outside air path.
2: There are typically two types of fan powered VAVs, either series or parallel. Your schematic shows the fan to not be in series with the airstream so that would be a parallel configuration in which typically the fan is only running when the zone calls for heat.
In a series configuration (not pictured) the fan is always running and the primary air from the AHU must pass through the fan. that is closer to how you described it which may be a little misleading.
3: Typically the duct static pressure sensor used to modulate the supply fan is mounted approximately 2/3 of the way down the primary air duct not at the end.
Anyways thanks for the video, nice work!
reply
Doc
We had to install some VAV boxes w their own EAC (Electronic Air Cleaner) in each due to the designated rooms having commercial computer systems, each box had it's own filter just before the EAC, the puter rooms had their own HVAC systems that were specified for more than the usual room specs since puters like cold air, twice to 3 times the usual for the room size but that's just bigger units, 'been there & done that' on other jobs. Although I'm familiar w this stuff it's fun to watch and I can share the vid sites to help non HVAC ppl understand the basic physics of it all and that's really what it comes down to but so many ppl don't grasp physics or weren't taught it. Gotta question the education system. Anyway great vid and great ch, keep up the good work.
reply
We had to install some VAV boxes w their own EAC (Electronic Air Cleaner) in each due to the designated rooms having commercial computer systems, each box had it's own filter just before the EAC, the puter rooms had their own HVAC systems that were specified for more than the usual room specs since puters like cold air, twice to 3 times the usual for the room size but that's just bigger units, 'been there & done that' on other jobs. Although I'm familiar w this stuff it's fun to watch and I can share the vid sites to help non HVAC ppl understand the basic physics of it all and that's really what it comes down to but so many ppl don't grasp physics or weren't taught it. Gotta question the education system. Anyway great vid and great ch, keep up the good work.
reply
Lance
Great Video, recently saw a 3rd floor building with return vents open to the area above the Drop ceiling. No return air ducting was visible. I assumed that the air was being sucked back thru the drop ceiling, it was about 4K sf. Is that legit, seems to be a really BAD idea since we're in the SF Bay Delta with tons of molding/rotting materials and dead grass and tree leaves on the ground everywhere, meaning pollen and mold/mildew spores whenever the wind blows. Between foot traffic of 3-600 people, and deliveries of boxes of equipment and paper. people are coughing and sneezing on that floor, even tho all the ceiling tiles have been replaced. I found about 8-8 return air Vent Tiles, but ZERO dedicated ducting. Thanks again!
reply
Great Video, recently saw a 3rd floor building with return vents open to the area above the Drop ceiling. No return air ducting was visible. I assumed that the air was being sucked back thru the drop ceiling, it was about 4K sf. Is that legit, seems to be a really BAD idea since we're in the SF Bay Delta with tons of molding/rotting materials and dead grass and tree leaves on the ground everywhere, meaning pollen and mold/mildew spores whenever the wind blows. Between foot traffic of 3-600 people, and deliveries of boxes of equipment and paper. people are coughing and sneezing on that floor, even tho all the ceiling tiles have been replaced. I found about 8-8 return air Vent Tiles, but ZERO dedicated ducting. Thanks again!
reply
Khalid
Firstly, great video as it outline the basics really well which allows a young professional to grow by asking question as they relate the animation to what they experience in the field.
My question is that I presently have a system with six VAVs installed on each of the main ducts leaving the AHU. Each duct(with its individual VAV) has further branches for individual rooms however it is controlled by a single thermostat sensor. So we receive frequent user complaints as the set point for the single thermostat sensor doesn't reflect the condition for all the room from that main duct.
Can you suggest a possible solution for the existing setup?
reply
Firstly, great video as it outline the basics really well which allows a young professional to grow by asking question as they relate the animation to what they experience in the field.
My question is that I presently have a system with six VAVs installed on each of the main ducts leaving the AHU. Each duct(with its individual VAV) has further branches for individual rooms however it is controlled by a single thermostat sensor. So we receive frequent user complaints as the set point for the single thermostat sensor doesn't reflect the condition for all the room from that main duct.
Can you suggest a possible solution for the existing setup?
reply
RabidLenny
Why does a VAV box need to calculate the air flowing through it?
Why could it not just be a motorized damper, with a PID controller, that is responding to the room thermostat temperature. If its to cold, it closes more towards its minimum position, if at minimum position, the heater turns on. If its too hot, it opens more and more, until room is at set point. Again, with a PID controller, as to not overshoot, but also not take too long to get to design.
reply
Why does a VAV box need to calculate the air flowing through it?
Why could it not just be a motorized damper, with a PID controller, that is responding to the room thermostat temperature. If its to cold, it closes more towards its minimum position, if at minimum position, the heater turns on. If its too hot, it opens more and more, until room is at set point. Again, with a PID controller, as to not overshoot, but also not take too long to get to design.
reply
Imran
I hope you are fine and doing well sir please clear me one thing if the VAVS is on auto mode heater and damper is on auto m ode set point is 28 and heater is ON desired and actual Air flow is same and damper position is accurate according to desired flow but Air supply temperature is not increasing upto 30 And space temperature is 23. I try to increase upto 25 but supply and space temperature is not increasing. why?
Please clear me in detail.
reply
I hope you are fine and doing well sir please clear me one thing if the VAVS is on auto mode heater and damper is on auto m ode set point is 28 and heater is ON desired and actual Air flow is same and damper position is accurate according to desired flow but Air supply temperature is not increasing upto 30 And space temperature is 23. I try to increase upto 25 but supply and space temperature is not increasing. why?
Please clear me in detail.
reply
Anas
Thank you
Question, I have a system in every apt kitchen where I need to set these VAVs to be operated and open damper when the kitchen exhaust hood is on to replace the 425CFM exhausted thru the hood
Note: owner wants to cut the cost of BMS system for individual apartment
- What is the easiest way to connect the actuator on the box to the the hood, and in the same time keep the thermostat controlling the normal operation?
reply
Thank you
Question, I have a system in every apt kitchen where I need to set these VAVs to be operated and open damper when the kitchen exhaust hood is on to replace the 425CFM exhausted thru the hood
Note: owner wants to cut the cost of BMS system for individual apartment
- What is the easiest way to connect the actuator on the box to the the hood, and in the same time keep the thermostat controlling the normal operation?
reply
Kazimir
I guess you're a part of my daily workday now. (I'm a photographer and sit hours infront of a PC.
What programm do you use for the animations? Would be really interested to look at it in detail by myself. I'm doing some research on biological recycling of energy in closed envirements. And you're helping me alot understand things I need to know. I nearly cant belive how helpfull this all is.
reply
I guess you're a part of my daily workday now. (I'm a photographer and sit hours infront of a PC.
What programm do you use for the animations? Would be really interested to look at it in detail by myself. I'm doing some research on biological recycling of energy in closed envirements. And you're helping me alot understand things I need to know. I nearly cant belive how helpfull this all is.
reply
Vronique
This is really clear! Thank you. I would like to know how does it work if you install an electric coil with a 24v relay that also controls the electric baseboards heaters that will be installed in each room if heating should be interlocked with the air conditioning.
reply
This is really clear! Thank you. I would like to know how does it work if you install an electric coil with a 24v relay that also controls the electric baseboards heaters that will be installed in each room if heating should be interlocked with the air conditioning.
reply
Farhan
Thanks for all the information u r providing here, it's very helpful for me, I would like to have some more videos on different types of central ac like package ac, split ac, and also cassette ac, thanks and I hope u will consider my request
reply
Thanks for all the information u r providing here, it's very helpful for me, I would like to have some more videos on different types of central ac like package ac, split ac, and also cassette ac, thanks and I hope u will consider my request
reply
Saif
Thank you for the video it is really helpful.
may i ask when would we require a VAV installed on the return as well as many designers are asking for it, it is really required? if yes in which applications it should be use?
reply
Thank you for the video it is really helpful.
may i ask when would we require a VAV installed on the return as well as many designers are asking for it, it is really required? if yes in which applications it should be use?
reply
Gary
Another superb video. Can you explain the basic relationship between FCUs and VAVs, i. e. is the HVAC system typically either one or the other, or are there installations where they can both be used in the same HVAC system?
reply
Another superb video. Can you explain the basic relationship between FCUs and VAVs, i. e. is the HVAC system typically either one or the other, or are there installations where they can both be used in the same HVAC system?
reply
Anthony
thx you for the video, but sometime the pressure sensor signal is not fast enough to send back to the VFD to slow down the AHU and it causes vibration issue. How can I speed up the pressure sensor signal to avoid it?
reply
thx you for the video, but sometime the pressure sensor signal is not fast enough to send back to the VFD to slow down the AHU and it causes vibration issue. How can I speed up the pressure sensor signal to avoid it?
reply
Mike
wow i am so thankful you made this video now i have a better understanding on how it all works together. i am about to graduate my HVAC/R this year. I, m really into this stuff
reply
wow i am so thankful you made this video now i have a better understanding on how it all works together. i am about to graduate my HVAC/R this year. I, m really into this stuff
reply
Osama
Thank you very much
Well explained
Can you make a video of the control method of VAV?
Also there is another type called bypass, you didn't mention in video.
reply
Thank you very much
Well explained
Can you make a video of the control method of VAV?
Also there is another type called bypass, you didn't mention in video.
reply
SP1
hello friend, this video is very interesting, I ask for your permission to translate it into Portuguese and be able to show my colleagues at HVAC here in Brazil, a hug
reply
hello friend, this video is very interesting, I ask for your permission to translate it into Portuguese and be able to show my colleagues at HVAC here in Brazil, a hug
reply
Zeeshan
Do we need to have vav on Return to control the exact mount of return from each room? its important especially when we need different pressure in different zones.
reply
Do we need to have vav on Return to control the exact mount of return from each room? its important especially when we need different pressure in different zones.
reply
Nisha
does VAV system give control over air exchange rate of every room? like can his allow one single ahu to supply at different air exchange rates for different rooms?
reply
does VAV system give control over air exchange rate of every room? like can his allow one single ahu to supply at different air exchange rates for different rooms?
reply
education
Thanks a lot for these usefull videos. but could you please take care of your accent since to get more formal since words are hard to understand. thanks again
reply
Thanks a lot for these usefull videos. but could you please take care of your accent since to get more formal since words are hard to understand. thanks again
reply
Chris
On some of the bigger buildings I find they use vav for cooling the interior space and FPT for the exterior with either electric reheat or hot water actuators
reply
On some of the bigger buildings I find they use vav for cooling the interior space and FPT for the exterior with either electric reheat or hot water actuators
reply
Al
Excellent video. In 20-25 years do you have to replace the whole box or is it most common to replace parts? Is 20-25 years the average life span of a VAV box?
reply
Excellent video. In 20-25 years do you have to replace the whole box or is it most common to replace parts? Is 20-25 years the average life span of a VAV box?
reply
Mohamed
Just i want to thank u very much for ur efforts. i am really enjoying ur explanation to the systems.
thank u very much Again. please keep going
reply
Just i want to thank u very much for ur efforts. i am really enjoying ur explanation to the systems.
thank u very much Again. please keep going
reply
Toyin
Thanks for the video.
can I conclude that VAV is only applicable to spaces with same thermal zone( space with more than one ventilation room)?
reply
Thanks for the video.
can I conclude that VAV is only applicable to spaces with same thermal zone( space with more than one ventilation room)?
reply
Earth+
As the supply volume flow rate varies, how does it make sure each zone recives minimum required fresh air volume flow rate? Thanks for the video!
reply
As the supply volume flow rate varies, how does it make sure each zone recives minimum required fresh air volume flow rate? Thanks for the video!
reply
esttaifan
So do you have to put a damper in the return duct in each space? Otherwise the ahu would suck back more air while the space is satisfied
reply
So do you have to put a damper in the return duct in each space? Otherwise the ahu would suck back more air while the space is satisfied
reply
Toyin
kudos for your clear explanation. Also, can you do a video or training on HVAC and ducts design I will so much appreciate if I can get this
reply
kudos for your clear explanation. Also, can you do a video or training on HVAC and ducts design I will so much appreciate if I can get this
reply
sharukhnizami
Thanks, very good,
Could u please detail the pressure independent VAV box, and how VFD will get feedback signal in this method
reply
Thanks, very good,
Could u please detail the pressure independent VAV box, and how VFD will get feedback signal in this method
reply
Mohsen
what the diffrent beetween fancoil and ahu? because is ahu we cool or heat the aire and again in fan coil we do that again. whay?
reply
what the diffrent beetween fancoil and ahu? because is ahu we cool or heat the aire and again in fan coil we do that again. whay?
reply
Ray
If all vav are closed, will there be an over pressure in the system? Will the main air handling unit slow down automatically?
reply
If all vav are closed, will there be an over pressure in the system? Will the main air handling unit slow down automatically?
reply
Shahbaz
Some time bms system give command to decrease temperature but vav dampers not work how can we solve this problem.
reply
Some time bms system give command to decrease temperature but vav dampers not work how can we solve this problem.
reply
Add a review, comment
Other channel videos















